Technical Specifications - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

Accessories
12.1 Expansion modules
12.1.3.1

Technical specifications

Power supply
Supply voltage
Current consumption (max.)
Power loss (max.)
Digital inputs
Number of digital inputs
Input type
Input current
Input signal - logical state "0"
Input signal - logical state "1"
Maximum frequency
Input signal delay
Auxiliary supply terminals + and - terminal
Auxiliary power supply at + and - 24 V DC (see tolerance graph in chapter Expansion module 2DI
Maximum current at + and -
Number of terminals
SSR output
Output type
Solid state output rating (at
60 °C)
Connection
Connecting terminals
Cable cross-section (min-max)
Tightening torque
Insulation
Impulse withstand voltage Uimp
Operating frequency impulse
withstand voltage
Ambient conditions
Operating temperature
Storage temperature
Relative humidity
Maximum degree of pollution
Overvoltage category
Altitude of environment (max.)
184
5 V DC (supplied through the ATC6300)
250 mA
1.25 W
2
Positive or negative
7 mA
Must be an open collector signal
≥ 17.6 V (for PNP type)
≤ 6.4 V (for NPN type)
2000 Hz (if the input is configured as a counter)
50 Hz (if input is configured as status)
≥ 50 ms
2DO (Page 182))
42 mA (protected against overload and short-circuit)
Note: If the maximum current is exceeded, the protection is ena-
bled and the voltage drops
2
Solid state relays (Opto-Mosfet)
Max. 55 mA at 40 V DC / 30 V AC
Removable / plug-in
0.2 ... 1.5 mm
(AWG 28 ... 14)
2
0.18 Nm (1.7 lbf-in)
4 kV
2 kV
-20 ... +60 °C
-30 ... +80 °C
< 80 % (IEC / EN 60068-2-70)
2
3
≤ 2000 m
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents