MODBUS communication
11.6 Data library
11.6.3

Commands (use with MODBUS function 06)

Address
4F00H
4F01H
4F02H
4F03H
4F04H
4F05H
4F06H
4F07H
2F00H
2F0AH
2F03H
2F07H
2FF0H
28FAH
Remote variables:
If you write AAh in the corresponding address, the remote variable is set to 1. If you enter
BBh, the remote variable is set to 0 and disabled accordingly.
Changing the operating mode
The following values must be sent to the address 2F00H in order to set the corresponding
operating mode:
Value
0
1
2
164
Word
Function
s
1
Enable remote variable 1
1
Enable remote variable 2
1
Enable remote variable 3
1
Enable remote variable 4
1
Enable remote variable 5
1
Enable remote variable 6
1
Enable remote variable 7
1
Enable remote variable 8
1
Change of operating mode
1
Simulation of pressing a key on the user interface
1
Value 01h: Memory in EEPROM
Value 04h: Reboot
Value 05h: Save and reboot
1
Value 00h: Reset ATC6300
Value 01h: Reset the ATC6300 and save in FRAM
1
Execution of the command menu
1
Value 01h: Save the setting of the real-time clock
Function
Enable OFF mode
Enable MAN mode
Enable AUT mode
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01