P06 - Parameter Line 1 - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

Parameterization
9.3 Parameters
9.3.6

P06 - Parameter Line 1

The default values for Line 1 and Line 2 are the same, only that they always refer to the
corresponding line.
P06 Pa-
Designation on ATC
rameter
display
Line 1
P06.01
Min voltage limit
P06.02
Min. voltage pick-up Limit threshold for resetting the minimum trip
P06.03
Min voltage delay
P06.04
Max voltage limit
P06.05
Max. voltage pick-
up
P06.06
Max voltage delay
P06.07
Presence delay
130
Description
Limit threshold for minimum trip voltage
– The first two parameters specify the minimum
voltage threshold limit and the related hystere-
sis upon restoration of power. P6.02 cannot be
set to a lower value than P6.01. P6.03 defines
the intervention delay of this safety mechanism
voltage
- see Parameter 06.01
Delay time for minimum voltage
- see Parameter 06.01
Limit threshold for maximum trip voltage
– The first two parameters specify the maxi-
mum voltage threshold limit and the related
hysteresis upon restoration of power. P6.05
cannot be set to a higher value than P6.04. If
P6.04 is set to OFF, the
maximum voltage measurement is disabled.
P6.06 specifies the maximum voltage interven-
tion delay.
Limit threshold for resetting the maximum trip
voltage
- see Parameter 06.04
Delay for maximum voltage
- see Parameter 06.04
Presence delay (when Line 2 source not avail-
able)
– Used if the energy source of Line 2 is not
available.
This defines after what time the ATC considers
the line to be stable (if within the limit thresh-
olds). During this time the LED Line 1 signals
availability.
Normally this time is shorter than P6.08, as the
load is non energized, and voltage needs to be
supplied urgently.
Unit
Default
Range
%
85
70-100
%
90
70-100
s
5
0-600
%
115
100-130 / OFF
%
110
100-130 / OFF
s
5
0-600
s
10
1-6000
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01