Status Of The Atc (Use With Modbus Function 03 And 04) - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

MODBUS communication
11.6 Data library
11.6.4

Status of the ATC (use with MODBUS function 03 and 04)

Address
2210H
The meaning of the 32 bits of the address 2210H can be viewed below:
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
166
Words
Function
2
Status of the ATC (bit 0 - bit 31)
Meaning
ATC OFF
ATC in MAN mode
ATC in AUT mode
ATC in Test mode
Voltage Line 1 OK
Voltage Line 2 OK
LED Line 1 enabled
LED Line 2 enabled
LED load on Line 1 enabled
LED load on Line 2 enabled
Mains breaker closed
Generator breaker closed
Global alarm
AC power supply
Start generator 1
Start generator 2
Line 1 maximum voltage
Line 1 minimum voltage
Line 1 maximum frequency
Line 1 minimum frequency
Line 1 phase failure
Line 1 phase unbalance
Line 2 maximum voltage
Line 2 minimum voltage
Line 2 maximum frequency
Line 2 minimum frequency
Line 2 phase failure
Line 2 phase unbalance
Not used
Not used
Not used
Not used
Format
unsigned integer
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents