Technical Specifications - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

12.1.6.1

Technical specifications

Power supply
Supply voltage
Current consumption (max.)
Power loss (max.)
RS485 port connection
Connecting terminals
Number of terminals
Cable cross-section (min-max)
Tightening torque
Insulation
Impulse withstand voltage U
Operating frequency impulse withstand
voltage
Ambient conditions
Operating temperature
Storage temperature
Relative humidity
Maximum degree of pollution
Overvoltage category
Altitude of environment (max.)
Enclosure
Enclosure material
Degree of protection
Weight
Certifications and approvals
The following standards are complied
with:
Complies with standards
UL marking
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
5 V DC (supplied through the ATC6300)
50 mA
0.25 W
Removable / plug-in
4
0.2 ... 1.5 mm
0.18 Nm (1.7 lbf-in)
7.3 kV
imp
4 kV
-20 ... +60 °C
-30 ... +80 °C
< 80 % (IEC / EN 60068-2-70)
2
3
≤ 2000 m
Polyamide RAL7035
IP20
50 g
cULus
RS485 output
Use 60 °C / 75 °C copper conductors only
AWG range: 28 - 14 AWG stranded or solid
Field wiring terminals tightening torque: 1.7 lbf-in
IEC / EN 61010-1
IEC / EN 61000-6-2
IEC / EN 61000-6-3
UL 508
SA C22.2-N°14
12.1 Expansion modules
(AWG 28 ... 14)
2
Accessories