Siemens SENTRON ATC6300 Manual page 198

Table of Contents

Advertisement

Technical specifications
Real-time clock
Energy storage
Operating period without power supply
Digital inputs: Terminals 15-20
Input type
Input current
Input signal - logical state "0"
Input signal - logical state "1"
Input signal delay
Relay outputs OUT1 and OUT2: Terminals 9, 10 and 11, 12
Contact type
Rated contact current
UL Rating
Output voltage (maximum)
Mechanical / electrical endurance (cycle)
Design of insulation
Insulation voltage U
Impulse withstand voltage U
Operating frequency impulse withstand volt-
age
Relay output OUT3: Terminals 22, 23, 24
Contact type
Rated contact current
UL Rating
Output voltage (maximum)
Mechanical / electrical endurance (cycle)
Insulation voltage U
Impulse withstand voltage U
Operating frequency impulse withstand volt-
age
196
i
imp
i
imp
Stored-energy capacitors
5 minutes
Negative
≤ 8 mA
≤ 2
≥ 3.4
≥ 50 msec
2x 1 NO contacts
AC1 8 A 250 V
DC1 8 A 30 V
AC15 1.5 A 250 V
B300
30 V DC 1A pilot duty
250 V AC
1x10^7 / 1x10^5
Single between OUT1 and OUT2
Double for the remaining groups
250 V AC
Single / double
4.8 kV / 7.3 kV
1.5 kV / 3 kV
1 CO contact
AC1 8 A 250 V
DC1 8 A 30 V
AC15 1.5 A 250 V
B300
30 V DC 1A pilot duty
250 V AC
1x10^7 / 1x10^5
250 V AC
7.3 kV
3 kV
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01

Hide quick links:

Advertisement

Table of Contents
loading