Alarm Description - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

Functions
5.1 Basic functions
5.1.6.2

Alarm description

The predefined alarms have the following properties:
Code
Description
A01
Battery voltage too low
A02
Battery voltage too high
A03
Line 1 circuit breaker
timeout
A04
Line 2 circuit breaker
timeout
A05
Line 1 wrong phase
sequence
A06
Line 2 wrong phase
sequence
A07
Load not powered
timeout
A08
External battery charger
failure
A09
Emergency
A10
Line 1 breaker protec-
tion trip
A11
Line 2 breaker protec-
tion trip
A12
Line 1 generator not
available
A13
Line 2 generator not
available
A14
Maintenance Hours 1
A15
Maintenance Hours 2
A16
Maintenance operations
1
A17
Maintenance operations
2
A18
Auxiliary voltage failure
UA1.
User alarm
UA4
48
Cause of alarm
The voltage of the DC supply is below the lower threshold limit for longer than the set
time.
The voltage of the DC supply is above the upper threshold limit for longer than the set
time.
The Line 1 switching device has not performed any opening or closing operation within
the set maximum period. Once the alarm has been triggered, the ON or OFF command
is inhibited. The alarms are only triggered if at least one of the two energy sources is
available, that is to say it is within the limits.
The Line 2 switching device has not performed any opening or closing operation within
the set maximum period. Once the alarm has been triggered, the ON or OFF command
is inhibited. The alarms are only triggered if at least one of the two energy sources is
available, that is to say it is within the limits.
The phase sequence measured on Line 1 does not match the programmed phase
sequence.
The phase sequence measured on Line 2 does not match the programmed phase
sequence.
Either because the power supplies were not available, or because both switching de-
vices have remained open, the load has been de-energized for longer than the time
programmed with P05.11.
This alarm is triggered by the input programmed for the charger alarm function if at
least one energy source is within the limits.
Alarm triggered by opening the external emergency input. Both switching devices are
opened (see Table of functions of the digital inputs (Page 108)).
The Line 1 breaker has opened because an overcurrent protection device has tripped.
This is signaled by activation of the input with function Line 1 breaker protection trip
(see Table of functions of the digital inputs (Page 108)).
The Line 2 breaker has opened because an overcurrent protection device has tripped.
This is signaled by activation of the input with function Line 2 breaker protection trip.
If the input with the function "Generator ready 1" is opened, this alarm is triggered (see
Table of functions of the digital inputs (Page 108)).
If the input with the function "Generator ready 2" is opened, this alarm is triggered (see
Table of functions of the digital inputs (Page 108)).
This alarm is triggered if the maintenance hours for Line 1 reach the value zero. See
Menu P12 - Miscellaneous (Page 139) Use this in order to reset operating hours and
alarm.
This alarm is triggered if the maintenance hours for Line 2 reach the value zero. See
Menu P12 - Miscellaneous (Page 139) Use this in order to reset operating hours and
alarm.
This alarm is triggered if the number of operating cycles for Line 1 reaches the value
set in Menu P12. Use command menu to restore operation and reset the alarm.
This alarm is triggered if the number of operating cycles for Line 2 reaches the value
set in Menu P12. Use command menu to restore operation and reset the alarm.
The device that manages the draw of auxiliary voltage supply from one of the available
lines signals a failure or improper operation.
The user alarm is generated by enabling the variable or associated input in Menu P15.
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents