General setting
Table: Output function
Param-
Setting
Con-
eter
nection
P05.07
Chg.
25
Pul.
27
28
30
If the 3VL molded case circuit breaker is used in combination with MO, the following
minimum parameters must be observed:
P05.06 Delay,
feedback signal
3VL8
5 s
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
Param-
Setting
eter
P11.04.
Open Line 1 circuit
01
breaker
P11.05.
Close Line 1 circuit
01
breaker
P11.06.
Open Line 2 circuit
01
breaker
P11.07.
Close Line 2 circuit
01
breaker
P06.07 Delay,
voltage present
5 s
7.3 Connection of Siemens SENTRON switching devices
Table: Input function
Con-
Param-
Setting
nection
eter
15
P10.01.
Line 1 breaker closed (feedback 1)
01
16
P10.02.
Line 2 breaker closed (feedback 2)
01
17
P10.03.
Line 1 circuit breaker protection (Trip
01
1)
18
P10.04.
Line 2 circuit breaker protection (Trip
01
1)
P06.08 Delay,
P07.07 Delay,
Line 2 OK
voltage present
5 s
5 s
Connection
P07.08 Delay,
Line 1 OK
5 s