5.1.6.1
Properties of the alarms
Various properties can be assigned to each alarm, including the user alarms (UAx see
chapter User alarms (Page 50)).
● Alarms enabled (active)
General enabling of the alarm.
If an alarm has not been enabled, the procedure is as if the alarm did not exist.
● Only AUT (Aut)
The alarm can only be triggered if the ATC6300 is in automatic mode.
● Retention alarm (Retent)
Remains stored, even after the triggering cause has been removed.
● Global alarm (Glb Al)
Activates the output which is assigned to this global alarm function (see chapter Table of
functions of the digital outputs (Page 112))
● Lock BRK1 (Lock 1)
On occurrence of the alarm, no further commands are sent to switching device 1.
● Lock BRK2 (Lock 2)
On occurrence of the alarm, no further commands are sent to switching device 2.
● Siren (Siren)
Activates the output assigned to this function, as configured in the Table of alarms
(Page 49)
● Inhibit (Inhib.)
The alarm can be temporarily deactivated by activating a programmable input with the
alarm inhibit function.
● No LCD (No LCD)
The alarm is managed normally, but not shown on the display.
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
Functions
5.1 Basic functions
47