MODBUS communication
11.6 Data library
The 16 bits of the status Function Inputs for the address 2178h have the following
meaning:
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
The 16 bits of the status Function Outputs for the address 207Ah have the following
meaning:
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
162
Status of function inputs
Line 1 breaker closed
Line 1 breaker trip
Not used
Line 2 breaker closed
Line 2 breaker trip
Not used
Transfer to secondary line
Inhibit automatic return to priority line
Emergency
Start generator
Generator Line 1 ready
Generator Line 2 ready
Keypad lock
Parameter setting lock
Not used
Alarms inhibition
Status function outputs
Open Line 1 contactor/circuit breaker
Close Line 1 contactor/circuit breaker
Open Line 2 contactor/circuit breaker
Close Line 2 contactor/circuit breaker
Global alarm
Start generator 1
Start generator 2
ATC ready
Load shed
Not used
Not used
Open Line 1 and Line 2
Minimum voltage coil Line 1
Minimum voltage coil Line 2
Line 1 OK
Line 2 OK
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01