Technical Specifications - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

Accessories
12.1 Expansion modules
12.1.4.1

Technical specifications

Power supply
Supply voltage
Current consumption (max.)
Power loss (max.)
Relay outputs
Contact type
Rated contact current (IEC 60947-5-1)
UL Rating (UL 508)
Operational voltage (maximum)
Mechanical/electrical endurance (cycle)
Connecting terminals
Cable cross-section (min-max)
Tightening torque
Conductor temperature (min.)
Insulation
Insulation voltage Ui
Impulse withstand voltage Uimp
- between the ATC and the outputs:
- between 2 relay outputs:
Operating frequency impulse withstand
voltage
- between the ATC and the outputs:
- between 2 relay outputs:
Ambient conditions
Operating temperature
Storage temperature
Relative humidity
Maximum degree of pollution
Overvoltage category
Altitude of environment (max.)
Enclosure
Enclosure material
Degree of protection
Weight
Certifications and approvals
The following standards are complied
with:
186
5 V DC (supplied through the ATC6300)
100 mA
0.5 W
2x 1 CO contacts
AC1 5 A 250 V
DC1 5 A 28 V
AC15 1.5 A 250 V
B300, R300, 28 V DC 5A resistive, 250 V AC 5 A resistive
250 V AC
3x10^6 / 1x10^5
Removable / plug-in
0.2 ... 2.5 mm
(AWG 28 ... 12)
2
0.5 Nm (4.5 lbf-in)
75 °C
250 V AC
7.3 kV
2.5 kV
4 kV
1.5 kV
-20 ... +60 °C
-30 ... +80 °C
< 80 % (IEC / EN 60068-2-70)
2
3
≤ 2000 m
Polyamide RAL7035
IP20
50 g
cULus
Manual, 03/2018, L1V30535632002A-01
3KC ATC6300 transfer control device

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents