Example:
A user limit LIM1 of the voltage V L1-N of Line 1 is to be defined. The upper limit should be
250 V AC, and the lower limit should be 220 V AC.
Setting:
LIM1 Reference measurement: V L1-N
Source: Line 1
Channel number: 1
Function: Min + Max
Upper limit: 250 V
Multiplier: 1
Delay: 0.0 s
Lower limit 220 V
Multiplier: 1
Delay: 0.0 s
You can find a more detailed description in chapter P13 - Limit thresholds (Page 140).