Operation
8.3 Designation and description of the outputs
8.3.2

Table of functions of the digital outputs

The table below lists all functions that can be assigned to the programmable digital outputs
OUTx.
Function
Disabled
Configurable
Close Line 1 contactor/circuit breaker
Open Line 1 contactor/circuit breaker
Close Line 2 contactor/circuit breaker
Open Line 2 contactor/circuit breaker
Open Line 1 and Line 2
Min coil Line 1
Min coil Line 2
Line 1 generator control
Line 2 generator control
ATC ready
Global alarm
Line 1 status
Line 2 status
Siren
Operating mode
OFF mode
MAN mode
AUT mode
Remote variable REM (x)
Limit threshold LIM (x)
Dummy (dummy load)
112
Description
Output disabled
Free configuration by the user.
Command to close the contactor/circuit breaker
of Line 1.
Command to open the circuit breaker of Line 1
with possible spring load.
Command to close contactor/circuit breaker of
Line 2.
Command to open the circuit breaker of Line 2
with possible spring load.
Open both circuit breakers / neutral position of
the transfer switching equipment with motor op-
erator.
Controls the undervoltage release by opening
breaker 1 before the spring load cycle.
Controls the undervoltage releases by opening
breaker 2 before the spring load cycle.
Control of the Start / Stop remote control of the
generator on Line 1.
Control of the Start / Stop remote control of the
generator on Line 2.
ATC in automatic mode, without alarms, ready to
switch.
Output enabled in the presence of any alarm with
the property "Global alarm enabled".
This output is enabled if all conditions for the
connection of the load to Line 1 have been met.
This output is enabled if all conditions for the
connection of the load to Line 2 have been met.
Supplies power to the siren for the acoustic sig-
nal.
This output is enabled if the ATC is in one of the
operating modes set with parameter P12.03.
Enabled if the ATC is in the OFF mode.
Enabled if the ATC is in the MAN mode.
Enabled if the ATC is in the AUT mode.
Output controlled by remote variable REMx
(x=1..8).
Output controlled by the status of the limit thresh-
old LIM(x), (x=1..4); defined by the Index parame-
ter.
This output is enabled if the automatic test is
performed with dummy load.
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01