Technical Specifications - Siemens SENTRON ATC6300 Manual

Table of Contents

Advertisement

Technical specifications

Auxiliary power supply: Terminal 13,14
Supply voltage U
Operating range
Operating frequency
Power loss (max.)
Power consumption (max.)
Interference strength against voltage dips
- without expansion modules
- with 2 expansion modules
Recommended fusible link
Insulation voltage U
Impulse withstand voltage U
Operating frequency impulse withstand volt-
age
DC power supply: Terminal 31, 32
Battery power supply
Operating range of battery power supply
Current consumption (max.)
Power loss (max.)
Voltage measuring inputs: Terminals 1-4 and 5-8
Nominal voltage U
Measuring range
Frequency range
Measuring method
Impedance of measuring input
Connection method
Measuring accuracy
Insulation voltage U
Impulse withstand voltage U
Operating frequency impulse withstand volt-
age
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
s
i
imp
(maximum)
e
i
imp
100 ... 240 V AC
110 ... 250 V DC
90 ... 264 V AC
93.5 ... 300 V DC
45 ... 66 Hz
3.8 W
9.5 VA
≤ 50 ms (at 110 V AC)
≤ 250 ms (at 220 V AC)
≤ 25 ms (at 110 V AC)
≤ 120 ms (at 220 V AC)
F1A (quick-response)
250 V AC
7.3 kV
3 kV
12 or 24 V DC
7.5 ... 33 V DC
230 mA at 12 V DC
120 mA at 24 V DC
3.2 W
480 V AC L-L (277 V AC L-N)
50 ... 576 V AC L-L (333 V AC L-N)
45 ... 65 Hz
True RMS
> 0.5 MΩ L-N
> 1.0 MΩ L-L
Single-phase, two-phase, or three-phase system
± 0.25 %, value range ± 1 digit
480 V AC
7.3 kV
3 kV
13
195

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents