F018
Preset Speed 1
Program  Frequency  Preset Speeds
Up to fifteen (15) output frequency values that fall within the Lower-Limit and
the Upper-Limit range may be programmed into the ASD and output as a
Preset Speed. This parameter assigns an output frequency to binary number
0001 and is identified as Preset Speed 1. The binary number is applied to
I1 – I4 of the ACE G9-120V-PCB to output the Preset Speed.
Perform the following setup to allow the system to receive Preset Speed
control input at the I1 – I4 terminals:
Program  Fundamental  Standard Mode Selection  Command Mode
1.
Selection  Terminal Board.
Program  Terminal  Input Terminals  I1 (set to Preset Speed 1; LSB
2.
of 4-bit count). Repeat for I2 – I4 (MSB of 4-bit count) as Preset Speed 2
– 4, respectively (all Normally Open).
Program  Frequency  Preset Speeds  Preset Speed 1 (set an output
3.
frequency as Preset Speed 1; repeat for Preset Speeds 2 – 15 as required).
Program  Pattern Run  Operation Mode  Preset Speed Operation
4.
Mode  Enabled/Disabled.
Select Enable to use the direction, accel/decel, and torque settings of the
Preset Speed being run. The torque settings used will be as defined in
F181
and as selected via the associated discrete input terminals V/f
Switching 1 and 2 in
Table 7 on pg.
Select Disabled to use the speed setting only of the Preset Speed being run.
5.
Place the system in the Remote mode (Local/Remote LED Off).
6.
Provide a Run command (activate F and/or R).
Activate I1 to run Preset Speed 1 (120 VAC to I1 = 0001 binary).
With I1 – I4 configured to output Preset Speeds
may be applied to I1 – I4 of the ACE G9-120V-PCB to run the associated
Preset Speed. If bidirectional operation is required F and R must be activated.
With I1 being the least significant bit of a binary count, the I1 – I4 settings will
produce the programmed speed settings as indicated in the Preset Speed Truth
Table to the right.
Preset Speeds are also used in the Pattern Run mode.
Preset Speed 2
Program  Frequency  Preset Speeds
This parameter assigns an output frequency to binary number 0010 and is
identified as Preset Speed 2. The binary number is applied to I1 – I4 of the
ACE G9-120V-PCB to output the Preset Speed (see
information on this parameter).
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
236.
(F115
– F118), 0001 – 1111
F018
for additional
Direct Access Number — F018
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Preset Speed Truth Table
I4
Preset
I3
I2
MSB
1
0
0
2
0
0
3
0
0
4
0
1
5
0
1
6
0
1
F170
7
0
1
8
1
0
9
1
0
10
1
0
11
1
0
12
1
1
13
1
1
14
1
1
15
1
1
Note: 1 = Terminal activated.
Direct Access Number — F019
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
F019
I1
Output
LSB
0
1
F018
1
0
F019
1
1
F020
0
0
F021
0
1
F022
1
0
F023
1
1
F024
0
0
F287
0
1
F288
1
0
F289
1
1
F290
0
0
F291
0
1
F292
1
0
F293
1
1
F294
87

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents