Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 36

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

Terminal Descriptions
Forward
26
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The programmable terminal assignments may be accessed and changed from their default settings as
or via the Direct Access method: Program  Direct Access  Applicable
mapped on
pg. 57
Parameter Number. See the section titled
applicable Direct Access parameter numbers.
For additional information on terminal assignments and default setting changes, see the sections titled
Default Setting Changes on pg. 40
See the section titled
Cable/Terminal/Torque Specifications on pg. 272
cable/terminal sizes and torque specifications when making ACE G9-120V-PCB connections.
F
— The default setting for this terminal is Forward run command. The F input terminal is activated
by applying 120 VAC to this terminal. This terminal may be programmed to any of the functions listed
in
Table 7 on pg. 236
(see F111).
R
— The default setting for this terminal is Reverse run command. The R input terminal is activated by
applying 120 VAC to this terminal. This terminal may be programmed to any of the functions listed in
Table 7 on pg. 236
(see F112).
I1
— The default setting for this terminal is Preset Speed 1 (see
terminal is activated by applying 120 VAC to this terminal. This terminal may be programmed to any of
the functions listed in
Table 7 on pg. 236
I2
— This input terminal may be programmed to any of the functions listed in
F112).
I3
— This input terminal may be programmed to any of the functions listed in
F115).
I4
— This input terminal may be programmed to any of the functions listed in
F116).
I5
— The default function assigned to this input terminal is Stop Limit-Switch Forward. Activating
this terminal applies the Stop command and may be used to indicate the end-of-travel on any axis via a
limit switch. The Stop command stopping method is selected at the
parameter. This input terminal may be programmed to any of the functions listed in
(see F117).
I6
— The default function assigned to this input terminal is Stop Limit-Switch Reverse. Activating
this terminal applies the Stop command and may be used to indicate the end-of-travel on any axis via a
limit switch. The Stop command stopping method is selected at the
parameter. This input terminal may be programmed to any of the functions listed in
(see F118).
RR
— The default function to which this analog input terminal is assigned is
setting. The RR terminal accepts a 0 – 10 VDC input signal that is used to control the function to which
this terminal is assigned. This input terminal may be programmed to control the speed or torque of the
motor via an amplitude setting or regulate by setting a limit. The gain and bias of this terminal may be
adjusted for application-specific suitability (see
RX
— The default function to which this analog input terminal is assigned is
setting. The RX terminal accepts a ±10 VDC input signal that is used to control the function to which
this terminal is assigned. This input terminal may be programmed to raise or lower the speed or torque
of the motor via an amplitude setting. This terminal may also be used to regulate the speed or torque of
Program Mode Menu Navigation on pg. 57
and
Terminal on pg.
60.
(see F115).
F210
– F215).
ACE-tronics G9 ASD Installation and Operation Manual
for the
for information on the proper
Preset Speed 1 on pg.
87). The I1 input
Table 7 on pg. 236
Table 7 on pg. 236
Table 7 on pg. 236
Limit-Switch Stopping Method
Table 7 on pg. 236
Limit-Switch Stopping Method
Table 7 on pg. 236
Frequency Mode 1
Torque Command
(see
(see
(see