Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 117

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

F198
V/f 5-Point Setting Frequency 5
Program  Special  V/f 5-Point Setting
The Custom V/f 5-Point Setting Frequency 5 sets the frequency to be
associated with the voltage setting of parameter
Voltage 5).
See
F190
and
F191
for additional information on this setting.
V/f 5-Point Setting Voltage 5
Program  Special  V/f 5-Point Setting
The V/f 5-Point Setting Voltage 5 establishes the output voltage level that is to
be associated with the frequency setting of
5).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this setting.
Frequency Priority Selection
Program  Fundamental  Standard Mode Selection
Either Frequency Mode 1 or Frequency Mode 2 may control the output
frequency of the ASD. This parameter determines which of the two will control
the output frequency and the conditions in which control will be switched from
one to the other.
Note:
Frequency Mode is abbreviated as FMOD.
Settings:
FMOD changed by Terminal Board (ACE G9-120V-PCB)
FMOD (F208)
The Frequency Mode 1 or Frequency Mode 2 selection specifies the source of
the input frequency command signal. These selections are performed at
and F207, respectively.
If FMOD changed by Terminal Board is selected here, the ASD will follow
the control of the discrete input terminal assigned the function of Frequency
Priority. The discrete terminal Frequency Priority will toggle control to and
from Frequency Mode 1 and Frequency Mode 2 with each activation/
deactivation.
If FMOD (F208) is selected here, the ASD will follow the control of the
Frequency Mode 1 setting for the duration that the commanded frequency of
the Frequency Mode 1 setting is greater than the setting of F208.
If the commanded frequency of the Frequency Mode 1 setting is less than or
equal to the setting of
F208
Mode 2.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F199
(V/f 5-Point Setting
F198
(V/f 5-Point Setting Frequency
the ASD will follow the setting of Frequency
Direct Access Number — F198
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F199
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
Direct Access Number — F200
Parameter Type — Selection List
Factory Default — FMOD (changed by
TB)
Changeable During Run — Yes
F004
F200
107

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents