F140
Input Terminal 1 (F) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in the F terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Input Terminal 2 (R) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in the R terminal
input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Input Terminal 3 (I1) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in the I1 terminal
input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Input Terminal 4 (I2) Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in the I2 terminal
input by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Input Terminal 5 – 12 Response Time
Program Terminal Input Terminal Delays
This parameter delays the response of the ASD to any change in the 5 – 12
terminal inputs by the programmed value (see waveforms at F140).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F140
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F141
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F142
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F143
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F144
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
F144
99