F447
Dynamic Braking Torque Limit 3 Level
Program  Torque  Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #3 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Power Running Torque Limit 4 Level
Program  Torque  Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #4 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Dynamic Braking Torque Limit 4 Level
Program  Torque  Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #4 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Accel/Decel Operation After Torque Limit
Program  Torque  Torque Limit
In a Crane/Hoist application that is operating using a mechanical brake, this
parameter is used to minimize the delay between the brake release and the
output torque reaching a level that can sustain the load.
This setting may reference time or the operating speed of the motor.
Settings:
In Sync with Accel/Decel
In Sync with Minimum Time
Power Running Stall Continuous Trip Detection Time
Program  Protection  Stall
This parameter is used to extend the Over-Voltage Stall (F305) and the Over-
Current Stall (F017) time settings.
162
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F447
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F448
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F449
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F451
Parameter Type — Selection List
Factory Default — In Sync with Accel/
Decel
Changeable During Run — Yes
Direct Access Number — F452
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 1.0
Units — Seconds
ACE-tronics G9 ASD Installation and Operation Manual
F452