F303
Number of Times to Retry
Program  Protection  Retry/Restart
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted for a qualified trip.
The trip conditions listed below will not initiate the automatic Retry/Restart
function:
Input Phase Loss (Input Phase Failure)
Output Phase Loss (Output Phase Failure)
Output Current Protection Fault
Output Current Detector Error
Load Side Over-Current at Start
Earth Fault (Ground Fault)
Over-Current During Acceleration
Arm Over-Current at Start-Up
DBR Resistor Over-Current
Low-Current
Voltage Drop In Main Circuit
EEPROM Data Fault (EEPROM Fault)
Flash Memory/Gate Array/RAM-ROM Fault
CPU Fault
Emergency Off (EMG)
Communication Error
Option Fault
Sink/Source Setting Error (not used with the ACE-tronics G9 ASD)
Over-Speed Error
Over-Torque
Key Error
External Thermal Error
Externally-Controlled Interrupt
See the section titled
System Setup Requirements on pg. 8
information on this setting.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F303
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 10
for additional
F303
139