F932
My Function Time Data 5
Program  My Function  My Function Data
This parameter is used to set the response delay of the My Function Time
Data 5 terminal.
The applied discrete input signal must be present at the input terminal of the
ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
My Function Count Data 1
Program  My Function  My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT1 (ON Timer).
COUNT1 (ON Timer) outputs a 1 upon reaching the threshold setting of this
parameter.
My Function Count Data 2
Program  My Function  My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT2 (ON Timer).
COUNT2 (ON Timer) outputs a 1 upon reaching the threshold setting at this
parameter.
Input Function Target 1
Program  My Function  My Function Unit 4
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 1
terminal.
This setting assigns the function of the programmable Input Function Target 1
terminal to any one of the user-selectable functions listed in
Table 10 on pg.
242, or
Table 12 on pg.
See
F977
for additional information on this parameter.
Input Function Command 1
Program  My Function  My Function Unit 4
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/Reset function.
Table 13 on pg. 247
lists the available selections. Their use and selection
requirements are described in an example at F977.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 9 on pg.
245.
Direct Access Number — F932
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
Direct Access Number — F933
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Direct Access Number — F934
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Direct Access Number — F935
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
241,
Direct Access Number — F936
Parameter Type — Selection List
Factory Default — 0 (NOP)
F936
217