Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 242

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

F987
Brake-Release Torque Reference
Program  Crane/Hoist  Closed Loop Hoist Control
This parameter sets the output torque level threshold that must be reached
within the time setting of the
initiate the Brake Release during normal operation.
This setting is also used as a reference during the count-down of the
Release Torque Stable
Time.
See
Figure 32 on pg. 235
for additional information on this parameter.
Brake-Release Torque (Proving) Time
Program  Crane/Hoist  Closed Loop Hoist Control
The output-torque level requirement for the brake-release function must be met
before the brake can release.
This parameter is used to set a time in which the
Reference
(F988) criteria must be achieved.
See
Figure 32 on pg. 235
for additional information on this parameter.
Brake-Release Torque Stable Time
Program  Crane/Hoist  Closed Loop Hoist Control
Once the brake signal is initiated this parameter sets the time that the output
torque level must remain at or above the torque level set at
brake is released.
See
Figure 32 on pg. 235
for additional information on this parameter.
Brake-Release Mechanical (Delay) Time
Program  Crane/Hoist  Closed Loop Hoist Control
This parameter sets the time for completing the
(F992).
See
Figure 32 on pg. 235
for additional information on this parameter.
Brake-Set Mechanical (Delay) Time
Program  Crane/Hoist  Closed Loop Hoist Control
Once the brake signal is initiated this parameter sets the time that must elapse
before the brake engages.
See
Figure 32 on pg. 235
for additional information on this parameter.
232
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Brake-Release Torque (Proving) Time
Brake-Release Torque
F987
Brake-Seized Pulse Check
Direct Access Number — F987
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
(F988) to
Minimum — 10.00
Maximum — 250.0
Brake-
Units — %
Direct Access Number — F988
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — No
Minimum — 0.5
Maximum — 10.0
Units — Seconds
Direct Access Number — F989
Parameter Type — Numerical
Factory Default — 0.20
Changeable During Run — Yes
before the
Minimum — 0.00
Maximum — 2.55
Units — Seconds
Direct Access Number — F990
Parameter Type — Numerical
Factory Default — 0.75
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Direct Access Number — F991
Parameter Type — Numerical
Factory Default — 0.50
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
ACE-tronics G9 ASD Installation and Operation Manual
F991

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents