F181
Overload Protection Level 4
Program  Motor  Motor Set 4
The Motor 4 Overload Protection Level parameter specifies the motor
overload current level for motor set 4. This value is entered as either a
percentage of the full-load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps (A/V) or it
may be set as a percentage of the ASD rating. The nameplate FLA of the motor
may be entered directly when Amps is selected as the unit of measurement (see
F701
to change the display unit).
The Motor 4 Overload Protection Level setting will be displayed in Amps if
the EOI display units are set to A/V rather than %.
V/f 5-Point Setting Frequency 1
Program  Special  V/f 5-Point Setting
The V/f 5-Point Setting Frequency 1 setting establishes the frequency that is
to be associated with the voltage setting of
1).
The V/f 5-Point settings define a custom volts per hertz relationship for the
startup output of the ASD.
To enable this function, set the V/f Pattern (F015) selection to the V/f 5-Point
Curve setting.
Custom V/f Curves may be useful in starting high inertia loads such as rotary
drum vacuum filters.
104
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F191
(V/f 5-Point Setting Voltage
ACE-tronics G9 ASD Installation and Operation Manual
Direct Access Number — F181
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10
Maximum — 100
Units — %
Direct Access Number — F190
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F190