Viewing Trip Information
In the event that the condition causing an Alarm does not return to the normal operating level within a
specified time, the ASD Faults and a Trip is incurred.
When a Trip occurs, the resultant error information may be viewed either from the LED screen, LCD
Fault screen
(Table 15 on pg.
Trip
History).
Trip Record at Monitor Screen
The at-trip condition of the last four incurred trips may be viewed on the Monitor screen. The Monitor
screen displays the records of up to four trips and catalogs each trip as Past Trip #1 through Past Trip #4
(see
pg.
56). Once reset (Type Reset), the trip records are erased. If no trips have occurred since being
powered up or since the last reset, None is displayed for each trip record.
The Monitor screen at-trip record is erased when the ASD is reset.
Note:
An improper ASD setup may cause some trips — reset the ASD to the Factory Default
settings before pursuing a systemic malfunction (Program  Utilities  Type Reset 
Reset to Factory Settings).
Trip History
The Trip History screen records the system parameters for up to 20 trips. The recorded trips are
numbered from zero to 19. Once the Trip History record reaches trip number 19, the oldest recorded trip
will be deleted with each new record stored (first-in first-out). The Trip # field may be selected and
scrolled through to view the recorded trip information for a given trip number. The monitored parameters
are listed in
Table 16
occurred).
1) Trip Number
2) Trip Type
3) Time and Date
4) Frequency at Trip
5) Output Current
6) Output Voltage
7) Direction
Trip records are comprised of the full list of monitored parameters (28).
Clearing a Trip
Once the cause of the trip has been corrected, performing a
operation.
The trip may also be cleared using either of the following methods:
• Cycling power (trip info may be saved via
• Pressing the Stop-Reset key twice,
• Remotely via the communications channel,
• Momentarily activating the RES terminal of the ACE G9-120V-PCB, or
• Via Program  Utilities  Type Reset  Clear Past Trip (clears Monitor screen records only).
260
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
254), Monitor screen, or the
as At-Trip Recorded Parameters (parameter readings at the time that the trip
Table 16. Trip History Record Parameters.
At-trip Recorded Parameters
8) Frequency Reference
9) Bus Voltage
10) Discrete Input Status
11) OUT1/OUT2/BRAKE Status
12) Timer
13) Post Compensation Frequency
14) Feedback (inst.)
screen (Program  Utilities 
Trip History
15) Feedback (1 sec.)
16) Torque
17) Torque Reference
18) Torque Current
19) Excitation Current
20) PID Value
21) Motor Overload
Reset
re-enables the ASD for normal
F602
if desired),
ACE-tronics G9 ASD Installation and Operation Manual
22) ASD Overload
23) DBR Overload
24) Motor Load
25) ASD Load
26) DBR Load
27) Input Power
28) Output Power