F377
PG Disconnection Detection
Program  Feedback  PG
This parameter Enables/Disables the system's monitoring of the PG connection
status when using encoders with line driver outputs.
Note:
The PG Vector Feedback Board option is required to use this
feature.
Settings:
Disabled
Enabled with Filter
Enabled (Detect Momentary Power Failure)
Simple Positioning Completion Range
Program  Feedback  PG
While operating in the Positioning Control mode, this parameter sets the range
of accuracy for a Stop command initiated via the ACE G9-120V-PCB.
If the setting is too low the stop may be too abrupt.
Autotune 1
Program  Motor  Vector Motor Model
This parameter sets the Autotune command status.
Selecting Reset Motor Defaults for this parameter sets parameters F410, F411,
F412, and
F413
to the factory default settings.
If selecting Autotune on Run Command, Autotune Initiated by Input
Terminal, or Autotune of Detail Parameters for this parameter set the Base
Frequency, Base Frequency Voltage, and the Motor Rated Revolutions to
the nameplate values of the motor to achieve the best possible Autotune
precision.
Settings:
Autotune Disabled
Reset Motor Defaults
Enable Autotune on Run Command
Autotuning by Input Terminal Signal (see
Motor Constant Auto Calculation
Slip Frequency Gain
Program  Motor  Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
154
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 7 on pg.
236)
ACE-tronics G9 ASD Installation and Operation Manual
Direct Access Number — F377
Parameter Type — Selection List
Factory Default — Enabled (Detect
Momentary Power Failure)
Changeable During Run — Yes
Direct Access Number — F381
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 1
Maximum — 4000
Direct Access Number — F400
Parameter Type — Selection List
Factory Default — Autotune Disabled
Changeable During Run — No
Direct Access Number — F401
Parameter Type — Numerical
Factory Default — 70
Changeable During Run — Yes
Minimum — 0
Maximum — 150
Units — %