Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 167

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

F416
Stall Prevention Factor 1
Program  Protection  Stall
This parameter is to be adjusted in the event that the motor stalls when operated
above the base frequency.
If a momentary heavy load occurs the motor may stall before the load current
reaches the stall prevention level setting of F601.
A drop in the supply voltage may cause fluctuations of the load current or may
cause motor vibration. A gradual adjustment of this parameter may alleviate
this condition.
Start with a setting of 85 at these parameters and gradually adjust them from
there one at a time until the desired results are produced.
Adjustments to this parameter may increase the load current of the motor and
subsequently warrant an adjustment at the Motor Overload Protection Level
setting.
Torque Command
Program  Torque  Torque Control
When operating in the Torque Control mode, this parameter allows the user to
select the source of the torque command signal.
Settings:
V/I
RR
RX
Panel Keypad
(F725
Setting)
RS485 2-Wire
RS485 4-Wire
Communication Option Board
RX2 Option (AI1)
Tension Torque Bias Input
Program  Torque  Torque Control
This parameter Enables/Disables the Tension Torque Bias input function.
This feature is enabled by selecting a Tension Torque Bias input signal source.
Settings:
Disabled
V/I
RR
RX
Panel Keypad (Not Used)
RS485 2-Wire
RS485 4-Wire
Communication Option Board
RX2 Option (AI1)
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F416
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 10
Maximum — 250
Direct Access Number — F420
Parameter Type — Selection List
Factory Default — Panel Keypad
Setting)
Changeable During Run — Yes
Direct Access Number — F423
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F423