F453
Dynamic Braking Stall Prevention Mode
Program  Protection  Stall
The function of this parameter is to disable the Over-Voltage Stall (F305) and
the Over-Current Stall (F017) function during regeneration only.
Application-specific conditions may occur that warrant disabling the Stall
function during regeneration.
Settings:
Disabled (Stall During Dynamic Braking)
Enabled (No Stall During Dynamic Braking)
Current Control Proportional Gain
Program  Feedback  PG
This parameter sets the sensitivity of the ASD when monitoring the output
current to control speed.
The larger the value entered here, the more sensitive the ASD is to changes in
the received feedback.
Speed Loop Proportional Gain
Program  Feedback  PG
During closed-loop operation, this parameter sets the response sensitivity of the
ASD when monitoring the output speed for control.
The larger the value entered here, the larger the change in the output speed for a
given received feedback signal.
Speed Loop Stabilization Coefficient
Program  Feedback  PG
During closed-loop operation, this parameter sets the response sensitivity of the
ASD when monitoring the output speed for control.
The larger the value entered here, the quicker the response to changes in the
received feedback.
Load Moment of Inertia 1
Program  Feedback  PG
This parameter is used for calculating accel/decel torque when compensating
for load inertia while operating in the Drooping Control mode.
Second Speed Loop Proportional Gain
Program  Feedback  PG
During closed-loop operation, this parameter sets the sensitivity of the ASD
when monitoring the output speed for control.
The larger the value entered here, the more sensitive the ASD is to changes in
the received feedback.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F453
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Direct Access Number — F458
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Direct Access Number — F460
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — No
Minimum — 1
Maximum — 9999
Direct Access Number — F461
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 1
Maximum — 9999
Direct Access Number — F462
Parameter Type — Numerical
Factory Default — 35
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Direct Access Number — F463
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — No
Minimum — 1
Maximum — 9999
F463