Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 29

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

Figure 4. The Grounding Capacitor
Switch is used on typeforms 230-volt
0.5 HP to 10 HP and the 25 and 30 HP/
460-Volt 1.0 HP to 250 HP.
The value may be set to Maximum
(default setting) or to Zero by pushing or
pulling the switch actuator, respectively.
Figure 5. The Grounding Capacitor
Switch is used on typeforms 230-volt
15 HP to 20 HP and the 40 HP to
60 HP/460-Volt 30 HP to 100 HP.
The value may be set to Large
(default setting) or Small by pushing
or pulling the switch actuator,
respectively.
Figure 6. The Grounding Capacitor Bar is
used on typeforms 230-volt 75 HP and the 100
HP/460-Volt 125 HP and the 150 HP.
The value may be set to Small (default setting)
or Large by connecting or disconnecting the
switching bar, respectively.
Figure 7. The Grounding Capacitor Screw is
used on typeforms 460-volt 175 HP and above.
The value may be set to Small (default setting)
or Large by placing the screw in the A position
or by placing the screw in the B position,
respectively.
ACE-tronics G9 ASD Installation and Operation Manual