Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 171

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

F442
Dynamic Braking Torque Limit 1
Program  Torque  Torque Limit
This parameter determines the source of the Regenerative Torque Limit
control signal.
If Setting is selected, the value set at
Settings:
V/I
RR
RX
F443
Setting
Dynamic Braking Torque Limit 1 Level
Program  Torque  Torque Limit
This parameter provides a value to be used as the Regeneration Torque Limit
1 if
F443
Setting is selected at parameter F442.
Set this parameter to 250% to disable this function.
Power Running Torque Limit 2 Level
Program  Torque  Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Dynamic Braking Torque Limit 2 Level
Program  Torque  Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #2 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Power Running Torque Limit 3 Level
Program  Torque  Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #3 motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F443
is used for this parameter.
Direct Access Number — F442
Parameter Type — Selection List
Factory Default —
F443
Setting
Changeable During Run — Yes
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 249.9
Units — %
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F445
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F446
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
F446
161