Table 4. ACE G9-120V-PCB Default Assignment Terminal Names and Functions.
Terminal
Input/Output
Name
F
Forward
R
Reverse
I1
Input 1 — Multifunctional programmable discrete input.
Discrete Input
I2
Input 2 — Multifunctional programmable discrete input.
Apply
I3
Input 3 — Multifunctional programmable discrete input.
120 VAC to
activate.
I4
Input 4 — Multifunctional programmable discrete input.
I5
Stop Limit-Switch Forward — Multifunctional programmable discrete input.
I6
Stop Limit-Switch Reverse — Multifunctional programmable discrete input.
OUT1
Brake Failure
OUT2
Brake Release
Switched
BRAKE-A
BRAKE relay (N.O.).
Output
BRAKE-B
BRAKE relay (N.C.).
BRAKE-C
BRAKE relay (Common).
RR
Multifunctional programmable analog input. (0.0 to 10 VDC input).
RX
Multifunctional programmable analog input (±10 VDC input).
V — Multifunctional programmable isolated analog voltage input (0 to 10
Analog Input
V/I
VDC input).
(Select V
Frequency Mode 2
or I via
isolated analog current input (4 [0] to 20 mADC input — 0 Hz to Maximum
SW2)
Frequency).
Output Current
AM
the ASD or to the magnitude of the function assigned to this terminal (see
Table 8 on pg. 240
Analog Output
Output Frequency
FM
output frequency of the ASD or to the magnitude of the function assigned to
this terminal (see
P24
24 VDC output (200 mA max.).
DC Output
PP
10.0 VDC/10 mA voltage source for the external use (e.g., potentiometer).
Frequency Pulse — Multifunctional programmable output pulse train of a
FP
Pulsed Output
frequency based on the output frequency of the ASD (see
IICC
Return for the isolated V/I input terminal.
Return for the AM, FM, RR, RX, P24, and the PP analog terminals.
CC
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Default Function
Terminal Descriptions on pg. 26
(Also See
Run Command — Multifunctional programmable discrete input.
Run Command — Multifunctional programmable discrete input.
— Multifunctional programmable discrete output.
— Multifunctional programmable discrete output.
(Default Setting) — I —Multifunctional programmable
— Voltage output that is proportional to the output current of
for assignment listing).
— Current or Voltage output that is proportional to the
Table 8 on pg.
240). Select Current or Voltage at F681.
Circuit Config.
)
Figure 10 on pg. 29.
Figure 16 on pg. 29.
Figure 19 on pg. 29.
Figure 11 on pg. 29.
Figure 12 on pg. 29.
Figure 13 on pg. 29.
Figure 18 on pg. 29
Figure 14 on pg.
Figure 15 on pg. 29.
Figure 17 on pg. 29.
Table 8 on pg.
240).
Do Not connect to
Earth Gnd or to each
other.
29.