F501
Deceleration Time 2
Program  Fundamental  Acc/Dec 1
This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz for the #2 Deceleration profile.
The Accel/Decel pattern may be set using F503. This parameter may be further
defined by the settings of
F506
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
actual deceleration times.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
– F509.
Direct Access Number — F501
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds