Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 111

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

F168
Output Terminal 10 (R3) Function
Program  Terminal  Output Terminals
This parameter is used to set the functionality of the R3 discrete output
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable R3 terminal to any one of
the user-selectable functions listed in
Output Terminal 11 (R4) Function
Program  Terminal  Output Terminals
This parameter is used to set the functionality of the R4 discrete output
terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable R4 terminal to any one of
the user-selectable functions listed in
Base Frequency 2
Program  Motor  Motor Set 2
The Base Frequency 2 setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The Base Frequency Voltage 2
parameter is set at F171.
This parameter is used only when the parameters for motor set 2 are configured
and selected. Motor set 2 may be selected by a properly configured input
terminal (see
Table 7 on pg.
For proper motor operation, the Base Frequency should be set for the
nameplate frequency of the motor.
Base Frequency Voltage 2
Program  Motor  Motor Set 2
The Base Frequency Voltage 2 setting is the Motor #2 output voltage at the
Base Frequency (F170). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation setting (F307).
This parameter is used only when the parameters for motor set 2 are configured
and selected. Motor set 2 may be selected by a properly configured input
terminal (see
Table 7 on pg.
Manual Torque Boost 2
Program  Motor  Motor Set 2
The Manual Torque Boost 2 function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the Base Frequency 2 setting (F170).
See parameter
F016
(Manual Torque Boost 1) for an explanation of torque
boost.
This parameter is used only when the parameters for motor set 2 are configured
and selected. Motor set 2 may be selected by a properly configured input
terminal (see
Table 7 on pg.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 10 on pg.
242.
Table 10 on pg.
242.
236).
236).
236).
Direct Access Number — F168
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
Direct Access Number — F169
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
Direct Access Number — F170
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Direct Access Number — F171
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 50.0
Maximum — 660.0
Units — Volts
Direct Access Number — F172
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
F172
101

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents