F660
Adding Input Selection
Program  Feedback  Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed Output Frequency.
Settings:
Disabled
V/I
RR
RX
Panel Keypad
RS485 2-Wire
RS485 4-Wire
Communication Option Board
RX2 Option (AI1)
Option V/I
UP/DOWN Frequency (ACE G9-120V-PCB)
Pulse Input (Option)
Pulse Input (Motor CPU)
Binary/BCD Input (Option)
Multiplying Input Selection
Program  Feedback  Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the commanded frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the commanded frequency.
If Setting (F729) is selected, the % value entered at parameter
the multiplier of the commanded frequency.
Settings:
Disabled
V/I
RR
RX
Setting (F729)
RX2 Option (AI1)
AM Output Terminal Function
Program  Terminal  Analog Output Terminals
This parameter is used to set the output function of the AM analog output
terminal. The AM analog output terminal produces an output current that is
proportional to the magnitude of the function assigned to this terminal. The
available assignments for this output terminal are listed in
AM Terminal Setup Parameters
F670
— Set AM Function
F671
— Calibrate AM Terminal
F685
— Output Response Polarity Selection
F686
— Bias Adjustment
186
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F660
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F661
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F729
is used as
Direct Access Number — F670
Parameter Type — Selection List
Factory Default — Output Current
Changeable During Run — Yes
Table 8 on pg.
240.