Flow Measurement Problems - Emerson Micro Motion 5700 Configuration And Use Manual

Transmitters with intrinsically safe outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Configuration and Use Manual
MMI-20039472
16.6.2 Loop test failed
Cause
Output not powered
Power supply problem
Wiring problem
Circuit failure
Recommended actions
1. Check the power supply and power supply wiring.
2. Verify the output wiring.
3. Contact customer service.
16.6.3 Discrete Output readings reversed
Cause
Wiring problem
Configuration does not match wiring
Recommended actions
1. Verify the output wiring.
2. Ensure that Discrete Output Polarity is set correctly.

16.7 Flow measurement problems

16.7.1 Flow rate reported as zero when flow is present
Cause
The process condition is below cutoff.
Recommended actions
Verify the cutoffs.
16.7.2 Flow indication at no flow conditions or zero offset
Cause
Misaligned piping (especially in new installations)
Open or leaking valve
Incorrect sensor zero
Recommended actions
1. Verify all of the characterization or calibration parameters.
Configuration and Use Manual
Troubleshooting
June 2019
219