Emerson Micro Motion 5700 Configuration And Use Manual page 89

Transmitters with intrinsically safe outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Configuration and Use Manual
MMI-20039472
7. Optional: For two-stage batching, set % Target or Quantity for the following parameters:
Two-stage batching is a batch that is run on a gas and liquid mixture flowing through a pipeline.
% Target
Quantity
Parameter
End Warning
Open Primary
Open Secondary
Close Primary
Configure batch presets using ProLink III
A batch preset is a predefined group of batching parameters. You can define and save up to six batch presets.
When you run a batch, you must choose a preset. You can modify the batch target before you run the batch.
All other settings are fixed.
Procedure
1. Choose Device Tools → Configuration → Batcher.
2. Set Preset Number to the number of the preset that you want to configure.
3. Set Preset Name to the name to be used for this preset.
The name can be up to eight characters in length. Valid characters include A–Z and 0–9.
4. Set Preset Target to the size of the batch.
When the transmitter has measured the specified amount and applied the selected form of AOC, it
closes the valve.
5. Optional: Set Preset End Warning Point to the point in the batch at which a Modbus coil will be set.
The end warning allows the transmitter to alert the operator to the end of batch. The operator can
prepare for the end of the batch, e.g., by adjusting the flow rate to avoid overflow.
6. Set Enable Preset as desired.
Option
Description
Enabled (On) The preset is available for use. You can select it to run a batch.
Configuration and Use Manual
Configure process measurement applications
The values for Open Primary, Open Secondary, Close Primary, and End
Warning are each configured as a percent of target.
The values for Open Primary and Open Secondary are each configured as
a quantity at which the valve should open. The values for Close Primary
and End Warning are each configured as a quantity that is subtracted
from the target.
Description
The % target or quantity level that must be reached to alert the operator
that a batch is ending.
The % target or quantity level that must be reached to open the primary
valve.
The % target or quantity level that must be reached to open the secondary
valve.
The % target or quantity level that must be reached to close the primary
valve. When configuring by quantity, the amount is referenced to the end
of the batch and not to the beginning of the batch.