Emerson Micro Motion 5700 Configuration And Use Manual page 77

Transmitters with intrinsically safe outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Configuration and Use Manual
MMI-20039472
Option
Description
Polling
The meter polls an external
device for temperature data.
This data will be available in
addition to the internal RTD
temperature data.
Digital
A host writes temperature data
communications
to the meter at appropriate
intervals. This data will be
available in addition to the
internal RTD temperature data.
Postrequisites
If you are using external temperature data, verify the external temperature value displayed in the Inputs
group on the ProLink III main window.
Need help?
If the value is not correct:
Ensure that the external device and the meter are using the same measurement unit.
For polling:
Verify the wiring between the meter and the external device.
Verify the HART tag of the external device.
For digital communications:
Verify that the host has access to the required data.
Verify that the host is writing to the correct register in memory, using the correct data type.
Configuration and Use Manual
Configure process measurement applications
Setup
a. Set Line Temperature Source to Poll for External Value.
b. Set Polling Slot to an available slot.
c. Set Polling Control to Poll as Primary or Poll as Secondary.
Option
Description
Poll as Primary
No other HART masters will be on the
network. The Field Communicator is
not a HART master.
Poll as Secondary Other HART masters will be on the
network. The Field Communicator is
not a HART master.
d. Set External Device Tag to the HART tag of the
temperature device.
e. Click Apply.
a. Set Line Temperature Source to Fixed Value or Digital
Communications.
b. Click Apply.
c. Perform the necessary host programming and
communications setup to write temperature data to the
meter at appropriate intervals.
June 2019
77