Configure process measurement applications
June 2019
Option
Description
Disabled (Off) The preset is not available for use. You cannot select it to run a batch. You can always
enable it at a later time.
Preset 1 is always enabled and cannot be disabled.
7. Optional: For two-stage batching, set % Target or Quantity for the following parameters:
Two-stage batching is a batch that is run on a gas and liquid mixture flowing through a pipeline.
% Target
Quantity
Parameter
End Warning
Open Primary
Open Secondary
Close Primary
Configure batch presets using the Field Communicator
A batch preset is a predefined group of batching parameters. You can define and save up to six batch presets.
When you run a batch, you must choose a preset. You can modify the batch target before you run the batch.
All other settings are fixed.
Procedure
1. Choose Configure → Manual Setup → Inputs/Outputs → Batcher → Setup Presets.
2. Select the preset that you want to configure.
3. Enable or disable the preset as desired.
Option
Description
Enabled (On) The preset is available for use. You can select it to run a batch.
Disabled (Off) The preset is not available for use. You cannot select it to run a batch. You can always
enable it at a later time.
Preset 1 is always enabled and cannot be disabled.
90
The values for Open Primary, Open Secondary, Close Primary, and End
Warning are each configured as a percent of target.
The values for Open Primary and Open Secondary are each configured as
a quantity at which the valve should open. The values for Close Primary
and End Warning are each configured as a quantity that is subtracted
from the target.
Description
The % target or quantity level that must be reached to alert the operator
that a batch is ending.
The % target or quantity level that must be reached to open the primary
valve.
The % target or quantity level that must be reached to open the secondary
valve.
The % target or quantity level that must be reached to close the primary
valve. When configuring by quantity, the amount is referenced to the end
of the batch and not to the beginning of the batch.