Configure A Discrete Output - Emerson Micro Motion 5700 Configuration And Use Manual

Transmitters with intrinsically safe outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Configuration and Use Manual
MMI-20039472
Procedure
1. Set Frequency Output Fault Action as desired.
Default: Downscale
Important
If you set Frequency Output Fault Action to None, the Frequency Output will be controlled by the
setting of Process Variable Fault Action. In most cases, if you set Frequency Output Fault Action to
None, you should also set Process Variable Fault Action to None.
2. If you set Frequency Output Fault Action to Upscale, set Frequency Fault Level to the desired value.
Default: 14500 Hz
Range: 10 Hz to 14500 Hz
Related information
Configure Process Variable Fault Action
Options for Frequency Output Fault Action
Label
Upscale
Downscale
Internal Zero
None (default)

8.4 Configure a Discrete Output

Use a Discrete Output to report specific meter or process conditions.
Depending on your purchase order and channel configuration, you may have 0–2 Discrete Outputs on the
transmitter. Channel C can be configured as Discrete Output 1, and Channel D can be configured as
Discrete Output 2.
The Discrete Outputs are configured independently, and they operate independently.
8.4.1 Configure Discrete Output Source
Menu → Configuration → Inputs/Outputs → Channel x → I/O Settings → Source
Display
Device Tools → Configuration → I/O → Outputs → Discrete Output → Source
ProLink III
Configure → Manual Setup → Inputs/Outputs → Channel x → Discrete Output x → DOx Source
Field Communicator
Configuration and Use Manual
Frequency Output behavior
Goes to configured Upscale value:
Default: 14500 Hz
Range: 10 Hz to 14500 Hz
0 Hz
0 Hz
Determined by the setting of Process Variable Fault Action
Integrate the meter with the control system
June 2019
143