Set Up Concentration Measurement - Emerson Micro Motion 5700 Configuration And Use Manual

Transmitters with intrinsically safe outputs
Hide thumbs Also See for Micro Motion 5700:
Table of Contents

Advertisement

Configuration and Use Manual
MMI-20039472
CTL
Correction factor based on line temperature and pressure at saturation conditions.
CTL is applied when the API referral application is configured for an E table.
Referred density
The measured density after CTL or CTPL has been applied.
API volume flow
The measured volume flow rate after CTL or CTPL has been applied. Also called
temperature-corrected volume flow.
Batch-weighted
One density value is recorded for each unit of flow (e.g., barrel, liter). The average is
average density
calculated from these values. The average is reset when the API totalizer is reset. Not
available unless a totalizer has been configured with Source set to Temperature-
Corrected Volume Flow.
Batch-weighted
One temperature value is recorded for each unit of flow (e.g., barrel, liter). The
average
average is calculated from these values. The average is reset when the API totalizer is
temperature
reset. Not available unless a totalizer has been configured with Source set to
Temperature-Corrected Volume Flow.
API volume total
The total API volume measured by the transmitter since the last API totalizer reset.
Also called temperature-corrected volume total. Not available unless a totalizer has
been configured with Source set to Temperature-Corrected Volume Flow.
API volume
The total API volume measured by the transmitter since the last API inventory reset.
inventory
Also called temperature-corrected volume inventory. Not available unless an inventory
has been configured with Source set to Temperature-Corrected Volume Flow.

5.2 Set up concentration measurement

The concentration measurement application calculates concentration from line density and line temperature.
5.2.1 Preparing to set up concentration measurement
The procedure for setting up concentration measurement application depends on how your device was
ordered and how you want to use the application. Review this information before you begin.
Requirements for concentration measurement
To use the concentration measurement application, the following conditions must be met:
The concentration measurement application must be enabled.
The API Referral application must be disabled.
The advanced phase measurement application must be disabled.
A concentration matrix must be loaded into one of the six slots on the transmitter.
Tip
In most cases, the concentration matrix that you ordered was loaded at the factory. If it was not, you have
several options for loading a matrix. You can also build a matrix.
Temperature Source must be configured and set up.
One matrix must be selected as the active matrix (the matrix used for measurement).
Configuration and Use Manual
Configure process measurement applications
June 2019
65