8 Integrate the meter with the control
system

8.1 Configure the transmitter channels

Menu → Configuration → Inputs/Outputs → Channel x
Display
Device Tools → Configuration → I/O → Channels → Channel x
ProLink III
Configure → Manual Setup → Inputs/Outputs → Channel x
Field Communicator
Your transmitter uses Channels A, B, C, and D to support the control system and communications. Channels C
and D are configurable.
Depending on your purchase order, some channels may not be activated on your device. To see which
channels are activated:
Using the display: Menu → About → Licenses
Using ProLink III: Device Information
Using the Field Communicator: Overview → Device Information → Licenses → Permanent Feature Set
→ Input/Output Channels
To activate additional channels, contact customer service.
Important
The channel configuration must match the I/O wiring.
Prerequisites
Plan your channel assignments before configuring channels. Not all combinations are supported. For
example:
You cannot have two discrete outputs and a Frequency Output.
For details, see
Channel
combinations.
If you plan to use dual-pulse mode, configure Channel C as Frequency Output 1, and Channel D as
Frequency Output 2.
Important
To avoid causing process errors:
Configure the channels before configuring the outputs.
Before changing the channel configuration, ensure that all control loops affected by the channel are under
manual control.
Procedure
1. Identify the channels that are activated on your device.
2. For Channel C and Channel D, if activated, set Channel Type as desired.
Configuration and Use Manual

Integrate the meter with the control system

June 2019
127