Example Of Application System Configuration - Omron Sysmac NX Series User Manual

Machine automation controller analog i/o units high-speed analog input units
Hide thumbs Also See for Sysmac NX Series:
Table of Contents

Advertisement

*1. The connection method for the Support Software depends on the model of the CPU Unit or Industrial PC.
Let-
ter
(A)
EtherCAT master
(B)
EtherCAT Coupler Unit
(C)
NX Units
(D)
End Cover
(E)
Support Software
(F)
ESI (EtherCAT Slave In-
formation) file
(G)
Communications cable
*1. An EtherCAT Slave Terminal cannot be connected to any of the OMRON CJ1W-NC£81/£82 Position Control
Units even though they can operate as EtherCAT masters.
*2. The term Support Software indicates software that is provided by OMRON.
Refer to 1-5 Support Software on page 1 - 12 for information on Support Software.
1-2-3

Example of Application System Configuration

The following figure shows an example of a characteristic inspection system configuration where an
NX-series High-speed Analog Input Unit is used.
The system reads analog input signals to detect abnormal noise, vibration and torque values through
the inspection, and determines whether the workpiece operation is acceptable or not.
It uses input from devices such as a photoelectric sensor as trigger input to efficiently obtain the ana-
log input data required for inspection.
In this way, you can configure a system based on a general-purpose Controller and perform character-
istics inspection without using special measuring equipment.
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
Item
The EtherCAT master manages the network, monitors the status of slaves,
*1
and exchanges I/O data with slaves.
The High-speed Analog Input Units can be connected with the following OM-
RON master products.
NJ/NX-series CPU Units
NY-series Industrial PCs (NX5££-1£00 and NY5££-5£00)
They cannot be connected to other manufacturers' master products, or other
OMRON master products.
The EtherCAT Coupler Unit serves as an interface for process data communi-
cations on the EtherCAT network between the NX Units and the EtherCAT
master.
The I/O data for the NX Units is accumulated in the EtherCAT Coupler Unit
and then all of the data is exchanged with the EtherCAT master at the same
time.
The EtherCAT Coupler Unit can also perform message communications (SDO
communications) with the EtherCAT master.
The NX Units perform I/O processing with connected external devices.
The NX Units perform process data communications with the EtherCAT mas-
ter through the EtherCAT Coupler Unit.
The End Cover is attached to the end of the Slave Terminal.
The Support Software runs on a personal computer and it is used to configure
*2
the EtherCAT network and EtherCAT Slave Terminal, and to program, moni-
tor, and troubleshoot the Controllers.
The ESI file contains information that is unique to the EtherCAT Slave Termi-
nal in XML format. You can load an ESI file into the Support Software to easily
allocate Slave Terminal process data and make other settings.
The ESI files for OMRON EtherCAT slaves are installed in the Support Soft-
ware. You can obtain the ESI files for the latest models through the Support
Software's automatic update function.
Use a double-shielded cable with aluminum tape and braiding of Ethernet cat-
egory 5 (100Base-TX) or higher, and use straight wiring.
1 Features and System Configuration
Description
1
1 - 7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac nx-had401Sysmac nx-had seriesSysmac nx-had402

Table of Contents