6 Input Range and Converted Values
Converted value
+32640
+32000
Fixed at the
lower limit in
case of -0.1 V
or less.
0
-640
-0.1 V
Input Range: 1 to 5 V
A voltage of 1 to 5 V is converted to a signed integer value (0 to 32000).
The resolution is 1/32000.
The input voltage range for which conversion is possible is 0.92 to 5.08 V and the converted value is a
signed integer value (-640 to 32640).
If the input value falls below the input range such as for a disconnection, and the input voltage is less
than 0.3 V, the disconnection detection function activates. At this time, the converted value will be
32767.
Converted value
(decimal)
+32640
+32000
Fixed at the
lower limit in
this range.
Disconnection
detected
below 0.3 V.
0
-640
+0.3 V
6 - 4
(decimal)
0 V
+1 V
+0.92 V
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
Fixed at the upper
limit in case of
+5.1 V or more.
Voltage
+5 V +5.1 V
Fixed at the upper
limit in case of
+5.08 V or more.
Voltage
+5 V +5.08 V