6 Input Range and Converted Values
Converted value
+32640
+32000
Fixed at the
lower limit
in this range.
Disconnection
detected
below 1.2 mA.
0
-640
+1.2 mA
6 - 6
(decimal)
+4 mA
+3.68 mA
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
Fixed at the upper limit
in case of +20.32 mA
or more.
Current
+20 mA
+20.32 mA