Two-wire sensor
V
: Power supply voltage
CC
V
: Sensor's output residual voltage
R
I
: Sensor control output (load current)
OUT
I
: Input current at trigger input terminal of the High-speed Analog Input Unit (Input current when
ON
the rated voltage is applied)
R: Bleeder resistor
 Relation between OFF Current at Trigger Inputs and Sensor Leakage Cur-
rent
The trigger inputs of the High-speed Analog Input Units can detect sensor output OFF only when
the following conditions are satisfied:
I
≤ I
OFF
leak
When I
is greater than I
leak
Use the following equation to calculate the bleeder resistance constant.
R ≤ (V
/I
OFF
OFF
Use the following equation to calculate the rated power of a bleeder resistor.
Rated power W of bleeder resistor ≥ (V
The voltages and currents related to the conditions for NPN type sensors are shown in the figure
below.
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
V
V
R
CC
I
I
OUT
in
R
, connect a bleeder resistor R.
OFF
) × V
/(I
× (V
/I
OFF
leak
OFF
OFF
CC
IOV
Unit that can supply I/O power
to the NX bus
IOG
IOV
High-speed Analog Input Unit
IN
IOG
) - V
)
OFF
2
- V
)
/R × 4 [allowable margin]
R
4 Installation and Wiring
4 - 29