Event name
NX Unit I/O Communications Error
Meaning
An I/O communications error occurred in an NX Unit.
Source
Depends on where the Support
Software is connected and the
system configuration.
Error attrib-
Level
utes
Recovery
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
For the NX bus of CPU Units
An error that prevents normal NX
bus communications occurred in
a CPU Unit.
An NX Unit is not mounted prop-
erly.
The power cable for the Unit
power supply is disconnected, or
the wiring from the Unit power
supply to the NX Units is incor-
rect.
The power cable for the Unit
power supply is broken.
The voltage of the Unit power
supply is outside the specified
range, or the capacity of the Unit
power supply is insufficient.
There is a hardware error in the
NX Unit.
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
Source details NX Unit
Minor fault
For the NX bus of CPU Units
When Fail-soft Operation Is Set to Stop
Reset the error in the NX Bus Function Module.
When Fail-soft Operation Is Set to Fail-soft
Reset error in the NX Unit.
For Communications Coupler Units
When Fail-soft Operation Is Set to Stop
If the errors are detected in the Controller, reset all of the errors in
the Controller.
If the errors are not detected in the Controller, reset errors in the
Communications Coupler Unit and NX Unit.
When Fail-soft Operation Is Set to Fail-soft
Reset errors in Communications Coupler Unit and NX Unit.
Continues.
Operation
Data type
---
Correction
Check the error that occurred in
the CPU Unit and perform the re-
quired corrections.
Mount the NX Units and End
Cover securely and secure them
with End Plates.
Wire the Unit power supply to the
NX Units securely.
If the power cable between the
Unit power supply and the NX
Units is broken, replace it.
Configure the power supply sys-
tem configuration correctly ac-
cording to the power supply de-
sign method.
If the error persists even after
you make the above correction,
replace the NX Unit.
9 Troubleshooting
Event code
80200000 hex
Detection tim-
ing
Log category
System
The NX Unit will continue to operate.
Input data: Updating input values stops.
Output data: The output values depend on the
Load Rejection Output Setting.
Name
---
Prevention
Take preventive measures
against the error that occurred in
the CPU Unit.
Mount the NX Units and End
Cover securely and secure them
with End Plates.
Wire the Unit power supply to the
NX Units securely.
None
Configure the power supply sys-
tem configuration correctly ac-
cording to the power supply de-
sign method.
None