Omron Sysmac NX Series User Manual page 243

Machine automation controller analog i/o units high-speed analog input units
Hide thumbs Also See for Sysmac NX Series:
Table of Contents

Advertisement

Details on Data Sheet
Unit name
High-speed Analog Input Unit
External connection
Screwless clamping terminal block (16 terminals ×2)
terminals
I/O refreshing method Synchronous I/O refreshing
Indicators
TS indicator, IN indicator
Analog
Number of
4 points
input
points
section
Input meth-
Differential input
od
Input range Voltage:
Current:
Input con-
version
range
Absolute
Voltage: ±15 V
maximum
Input current: ±30 mA
rating
Input Impe-
Voltage: 1 MΩ min.
dance
Current: 250 Ω
Resolution
Over
25°C ±0.1% (full scale)
all
0 to
±0.2% (full scale)
ac-
55°C
cu-
racy
Conversion
5 µs per channel
time
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
-10 to 10 V
-5 to 5 V
0 to 10 V
0 to 5 V
1 to 5 V
0 to 20 mA
4 to 20 mA
Input range of -10 to 10 V or -5
to 5 V
-1% to 101% (full scale)
Other input ranges
-2% to 102% (full scale)
Input range of -10 to 10 V or -5
to 5 V
1/64000 (full scale)
Other input ranges
1/32000 (full scale)
*1
Model
NX-HAD401
Trigger
Number of
4 points
input
points
section
Internal I/O
NPN
common
Rated input
24 VDC (20.4 to 28.8 VDC)
voltage
Input cur-
3.5 mA typical (24 VDC)
rent
ON volt-
15 VDC min./3 mA min. (between
age/ON
IOV and each signal)
current
OFF volt-
5 VDC max./1 mA max. (between
age/OFF
IOV and each signal)
current
ON/OFF re-
1 μs max./1 μs max.
sponse
time
Input filter
No filter, 4 µs, 8 µs (default), 16
time
µs, 32 µs, 64 µs, 128 µs, 256 µs
Appendices
A
A - 5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac nx-had401Sysmac nx-had seriesSysmac nx-had402

Table of Contents