Event name
Unit I/O Disconnection Detected for Channel 1
Meaning
A disconnected input was detected for channel 1.
Source
Depends on where the Support
Software is connected and the
system configuration.
Error attrib-
Level
utes
Recovery
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
Input wiring is broken.
Input wiring is disconnected.
Attached in-
None
formation
Precautions/
You can change the event level to the observation level.
Remarks
Event name
Unit I/O Disconnection Detected for Channel 2
Meaning
A disconnected input was detected for channel 2.
Source
Depends on where the Support
Software is connected and the
system configuration.
Error attrib-
Level
utes
Recovery
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
Input wiring is broken.
Input wiring is disconnected.
Attached in-
None
formation
Precautions/
You can change the event level to the observation level.
Remarks
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
Source details NX Unit
Minor fault
Reset error in the NX Unit.
Continues.
Operation
Data type
---
Correction
Check the input wiring for breaks
and replace the cable if any are
found.
Check the input wiring for bad
connections and reconnect any
bad connections that are found.
Source details NX Unit
Minor fault
Reset error in the NX Unit.
Continues.
Operation
Data type
---
Correction
Check the input wiring for breaks
and replace the cable if any are
found.
Check the input wiring for bad
connections and reconnect any
bad connections that are found.
9 Troubleshooting
Event code
65030000 hex
Detection tim-
ing
Log category
System
The converted value will be 32,767.
Operation continues and the converted value re-
turns to normal when the connection is restored.
Name
---
Prevention
Check the cable for broken
wires.
Make sure that the wiring is con-
nected properly.
Event code
65040000 hex
Detection tim-
ing
Log category
System
The converted value will be 32,767.
Operation continues and the converted value re-
turns to normal when the connection is restored.
Name
---
Prevention
Check the cable for broken
wires.
Make sure that the wiring is con-
nected properly.
Continuously
Continuously
9
9 - 21