4 Installation and Wiring
 Relation between Input Current at Trigger Input Terminals and Sensor
Control Output (Load Current)
The trigger inputs of the High-speed Analog Input Units can detect sensor output ON only when the
following conditions are satisfied:
I
(min) ≤ I
OUT
I
(min): Minimum value of load current
OUT
I
(max): Maximum value of load current
OUT
Use the following equation to calculate the input current:
I
= I
in
ON
Note At the trigger input terminals of the High-speed Analog Input Units, the input current does not increase
linearly for the input voltage. If you gradually raise the input voltage and once the input current reaches
I
, the input current does not increase any further, and remains roughly constant even when the input
ON
voltage is raised.
When I
is smaller than I
in
be calculated as follows: Select an appropriate bleeder resistor R so that both equations can be
satisfied.
R ≤ (V
- V
CC
Rated power W of bleeder resistor ≥ (V
The voltages and currents related to the conditions for NPN type sensors are shown in the figure
below.
Two-wire sensor
The voltages and currents related to the conditions for PNP type sensors are shown in the figure
below.
4 - 28
≤ I
(max)
in
OUT
(min), connect a bleeder resistor R. The bleeder resistor constant can
OUT
)/(I
(min.) - I
)
R
OUT
ON
R
V
I
I
CC
OUT
in
V
R
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
2
- V
)
/R × 4 [allowable margin]
CC
R
IOV
Unit that can supply I/O power
to the NX bus
IOG
IOV
IN
High-speed Analog Input Unit
IOG