8 Functions
An execution confirmation dialog box is displayed.
6
Click the Yes Button. When the writing is completed successfully, the following dialog box is
displayed. Click the OK Button.
Additional Information
• A new calibration value is reflected immediately after you write it.
• When you write a calibration value, if the voltage or current that is input to the Unit terminal is
outside the correctable range, a dialog box as shown below will be displayed and calibration
will fail.
Resetting the Calibration Value to the Default
This section describes how to reset the calibration value to the default.
8 - 36
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)