Event name
Analog Unit Calibration Parameter Error
Meaning
An error occurred for the calibration data in the Analog Unit.
Source
Depends on where the Support
Software is connected and the
system configuration.
Error attrib-
Level
utes
Recovery
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
The power supply to the Analog
Unit was turned OFF or Support
Software communications were
disconnected while writing the
calibration values to the Analog
Unit.
Attached in-
None
formation
Precautions/
None
Remarks
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
Source details NX Unit
Minor fault
For the NX bus of CPU Units
When Fail-soft Operation Is Set to Stop
Restart the NX Unit and then reset the error in the NX Bus Function
Module.
When Fail-soft Operation Is Set to Fail-soft
Restart the NX Unit.
For Communications Coupler Units
When Fail-soft Operation Is Set to Stop
Restart the NX Unit.
If the errors are detected in the Controller, reset all of the errors in
the Controller.
When Fail-soft Operation Is Set to Fail-soft
Restart the NX Unit.
Continues.
Operation
Data type
---
Correction
Write the calibration values to the
Analog Unit again.
9 Troubleshooting
Event code
10400000 hex
Detection tim-
ing
Log category
System
I/O refreshing for the NX Unit stops.
Name
---
Prevention
Do not turn OFF the power sup-
ply to the Analog Unit or discon-
nect Support Software communi-
cations while writing the calibra-
tion values to the Analog Unit.
When power is